Datasheet

750-652
1
275
1.7
Serial Interface RS-232 / RS-485
Configurable
Delivered without miniature WSB markers
D0 D1
13 14
750-652
D2 D3
MM
S
S
TxD (RS-232)
Y (RS-485/422)
RS ... enabled
Flow control enabled
User LED 1
User LED 0
Data contacts
Function
Transmission status
Reception status
Error (buffer full)
RTS (RS-232)
Z (RS-485/422)
CTS (RS-232)
B (RS-485/422)
Power jumper contacts
Common
(ground)
RxD (RS-232)
A (RS-485/422)
Common
(ground)
Shield
(screen)
Shield
(screen)
TxD/YRTS/Z
RxD/A
CTS/B RTS/Z
TxD/Y
4 x 270 pF
10 nF
1 MΩ
RxD/A
CTS/B
24 V
0 V
750-652
Shield
(screen)
Shield
(screen)
Logic
Reception Transmission
Operating mode
(RS-232/-485)
Flow control
Function
Common
(ground)
Common
(ground)
The serial interface module connects RS-485/422 or RS-232 C interface
devices to the WAGO-I/O-SYSTEM 750. It also provides gateways between
the serial interface and the fieldbus systems supported by the
WAGO-I/O SYSTEM 750. No higher protocol level is required by the module.
Communication to the associated fieldbus master is completely transparent.
This provides for a broader application scope for the serial interface module.
If required, communication protocols can be configured via fieldbus master.
The 2560 byte input buffer provides for high data baud rates. At lower baud
rates, the data received in lower priority tasks is evaluated without data loss.
The 512 byte output buffer provides fast transmission of larger data strings.
The module can be configured via WAGO-I/O-CHECK or GSD files.
Flexible baud rate and data width selection provides perfect adaptation to the
respective application.
Compatibility with couplers/controllers:
See manual, Section 3 "Device Description"
Description
Item No.
Pack.
Unit
RS-232 / RS-485 configurable 750-652 1
RS-232 / RS-485 configurable/T 750-652/025-000 1
(Operating temperature -20 °C ... +60 °C)
Accessories
Item No.
Pack.
Unit
WAGO-I/O-CHECK, RS-232 kit 759-302 1
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Also see "Approvals Overview" in Section 1
Conformity marking 1
Shipbuilding (versions upon request) ABS, DNV, GL, KR
r UL 508
Technical Data
Transmission channels 1 TxD / 1 RxD, full duplex, half duplex
7 or 8 bit data, 1 or 2 stop bit
Baud rate 9,600 baud (default setting)
300 baud ... 115,200 baud
Bit transfer RS-485/-422: ISO 8482 /
DIN 66259 - 4; RS-232: EIA/TIA-232-F
Line length RS-485/-422: max. approx. 1000 m
twisted pair, RS-232: max. 40 m
Buffer 2560 bytes in / 512 bytes out
Current consumption (internal) 85 mA
Power supply via system voltage DC/DC
Isolation 500V system/supply
Internal bit width 1 x 46/1 x 24/1 x 6 bytes in/out
(parametrizable), 2 bytes control/status
Wire connection CAGE CLAMP
®
Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped lengths 8 ... 9 mm / 0.33 in
Width 12 mm
Weight 51 g
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 18.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com