Technical data
Table Of Contents
- 1 Important Notes
- 2 I/O Modules
- 3 Use in Hazardous Environments
- 3.1 Marking Configuration Examples
- 3.2 Installation Regulations
- 3.2.1 Special Conditions for Safe Operation of the ATEX and IEC Ex (acc. DEMKO 08 ATEX 142851X and IECEx PTB 07.0064)
- 3.2.2 Special conditions for safe use (ATEX Certificate TÜV 07 ATEX 554086 X)
- 3.2.3 Special conditions for safe use (IEC-Ex Certificate TUN 09.0001 X)
- 3.2.4 Special conditions for safe use (ATEX Certificate DEKRA 11ATEX0203 X)
- 3.2.5 ANSI/ISA 12.12.01

750-630 (/xxx-xxx) [SSI Transmitter Interface] • 15
Technical Data
WAGO-I/O-SYSTEM 750
I/O Modules
The following Ex approvals have been granted to the basic version of 750-630
I/O modules and the variation 750-630/000-xxx:
KEMA (01 KEMA 1024X) II 3 G EEx nA II T4
C
UL
US
(ANSI/ISA 12.12.01) Class I Div2 ABCD T4
The following Ex approvals have been granted to the variation 750-630/003-
000:
TÜV (07 ATEX 554086 X)
I M2 Ex d I
II 3 G Ex nA IIC T4
II 3 D Ex tD A22 IP6X T135°C
Permissible operation temperature: 0 °C ≤ TA ≤ +60 °C
TÜV (TUN 09.0001X)
Ex d I
Ex nA IIC T4
Ex tD A22 IP6X T135°C
Permissible operation temperature: 0 °C ≤ TA ≤ +60 °C
C
UL
US
(ANSI/ISA 12.12.01) Class I Div2 ABCD T4
More Information
Detailed references to the approvals are listed in the document "Overview
Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM
ELECTRONICC Tools and Docs (Item-No.: 0888-0412)
or in the internet under: http://www.wago.com Documentation
WAGO-I/O-SYSTEM 750 System Description