Technical data
Table Of Contents
- 1 Important Notes
- 2 I/O Modules
- 3 Use in Hazardous Environments
- 3.1 Marking Configuration Examples
- 3.2 Installation Regulations
- 3.2.1 Special Conditions for Safe Operation of the ATEX and IEC Ex (acc. DEMKO 08 ATEX 142851X and IECEx PTB 07.0064)
- 3.2.2 Special conditions for safe use (ATEX Certificate TÜV 07 ATEX 554086 X)
- 3.2.3 Special conditions for safe use (IEC-Ex Certificate TUN 09.0001 X)
- 3.2.4 Special conditions for safe use (ATEX Certificate DEKRA 11ATEX0203 X)
- 3.2.5 ANSI/ISA 12.12.01

14 • 750-630 (/xxx-xxx) [SSI Transmitter Interface]
Technical Data
WAGO-I/O-SYSTEM 750
I/O Modules
2.1.1.6 Technical Data
Module Specific Data
Transmitter connection Inputs: + D, -D, Outputs: +CL, -CL
Current consumption
typ.
(internal) 85 mA
Voltage via power jumper contacts DC 24 V (-15 % ... +20 %)
Transmission rate 125 kHz (max. 1 MHz)
Serial Input max. 32 bit width (adjustable)
Signal output (+CL, -CL) differential signal (RS 422)
Signal input (+D, -D) differential signal (RS 422)
Code Gray / Bin
Internal bit width 1 x 32 bits (24 bit used, 8 bit reserved)
2 x 8 bits control/status (option)
Isolation 500 V (System/Supply)
Dimensions W x H* x L
* from upper edge of 35 DIN rail
12 mm x 64 mm x 100 mm
Weight ca. 55 g
Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual)
Conformity Marking
C
UL
US
(UL508)