Datasheet
750-628
1
329
1.8
Internal Data Bus Extension Coupler Module
Delivered without miniature WSB markers
Data contacts
Matching
resistor
switch
RJ 45
connection
input
Module
bus status
RUN
ERROR
RJ-45
connection
output
Power jumper
contacts
0 V
Supply via
power jumper
contacts
24 V
Supply
24 V
0 V
Status
voltage supply
-Power jumper
contacts
-System
24V 0V
++
—
—
01
02
C
D
B
A
750-628
The coupler module for the internal data bus extension module 750-628 replaces
the fieldbus coupler/controller at an I/O terminal block. It is also the mating piece
for the end module 750-627. Plug the connecting cable into the top RJ-45 socket to
establish the logical link to the fieldbus coupler/controller via end module 750-627.
The extension is completely transparent for the fieldbus coupler/controller. All of the
functions of the I/O module system are retained without any changes. A further
extension to the system is provided by the bottom RJ-45 socket. This enables the
entire system to be extended by 10 stages.
The supply voltage for the field side and the internal electronics can be input
separately. Both levels are electrically isolated from each other. Two diagnostic LEDs
give information about the supply voltage for both the internal and field side. Two
LEDs in the input socket indicate fault-free communication with the bus coupler. The
extension module can be used as the last coupler module in the system (switch on
matching resistor) or as a bridge between two I/O module assemblies.
Installation note Attention:
To ensure safe, reliable operating states when using the internal data bus extension
750-627/-628 these states must be registered prior to startup with the following
couplers or PLCs (refer to manual for supported couplers/PLCs). You must use the
"WAGO Extension Setting" software for this (download: www.wago.com).
Please note that only one terminating resistor may be activated in the whole system.
Please complete the manufacturing number matrix on the right-hand side of the
couplers when updating the firmware and internal operating parameters.
Description
Item No.
Pack.
Unit
Internal Data Bus Extension Coupler
Module
750-628 1
Accessories
Item No.
Pack.
Unit
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Also see "Approvals Overview" in Section 1
Conformity marking 1
Shipbuilding GL
r UL 508
Technical Data
Max. no. of I/O modules 64 (in the whole system)
Buscoupler connection 2 x RJ-45 socket (input + output)
Distance 5 m (10 m see manual),
(end module and coupler or coupler and
coupler)
Transmission medium shielded copper wire
(ETHERNET patch cable)
4 x 2 x 0.25 mm²,
twisted pair, double shielding
Power supply 24 V DC (-15 % ... +20 %)
Max. input current (24 V) 200 mA
Efficiency of the power supply 76 %
Inrush current 2.5 x continuous current
Internal current consumption (5 V) 150 mA
Total current for I/O modules (5 V) 400 mA
Voltage via power jumper contacts 24 V DC (-15 % ... +20 %)
Current via power jumper contacts (max.) DC10 A
Isolation 500 V system/supply
Wire connection CAGE CLAMP
®
Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped lengths 8 ... 9 mm / 0.33 in
Width 25 mm
Weight 74.5 g
EMC: 1 - immunity to interference acc. to EN 61000-6-2 (2005)
EMC: 1 - emission of interference acc. to EN 61000-6-4 (2007)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 18.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com