Datasheet
750-472, 750-474 / 753-472, 753-474
1
231
1.5
2-Channel Analog Input Module 0/4-20 mA
Single-ended (S.E.)
Fig. 750 Series/Technical data see page 24/Delivered without miniature WSB markers
750/753 Series marking see pages 10 ... 11 / 12 ... 13
AI 2
Data contacts
Error AI 2
24 V
Shield
(screen)
Error AI 1
Function AI 1
AI 1
Shield
(screen)
0 V
Function AI 2
Power jumper contacts
E1
E2
13 14
C
D
B
A
+ +
0V 0V
S
S
750-472
AI 2
AI 1
Shield
(screen)
AI
Shield
(screen)
Logic
A
D
Function
I
0 V
24 V
24 V
0 V
Error
10nF
270pF
750-472
1
2
3
4
5
6
7
8
The analog input module powers the transducers, receives transmitted analog
signals, and with electrical isolation, transmits the signals to the fieldbus.
The 24V supply for the field is derived from the module's power jumper
contacts.
The shield (screen) is directly connected to the DIN rail.
At approx. 25mA, the overload protection switches the measurement input
to a high-resistance state. Under normal operating conditions it will
automatically switch back.
This input module can supply the voltage for 2-wire transducers.
Description
Item No.
Pack.
Unit
2AI 0-20mA 16 Bit S.E. 750-472 1
2AI 0-20mA 16 Bit S.E. S5
1)
750-472/000-200 1
2AI 0-20mA 16 Bit S.E. 60Hz 750-472/005-000 1
2AI 4-20mA 16 Bit S.E. 750-474 1
2AI 4-20mA 16 Bit S.E. S5
1)
750-474/000-200 1
2AI 4-20mA 16 Bit S.E. 60Hz 750-474/005-000 1
2AI 0-20mA 16 Bit, S.E. (without 753-472 1
2AI 4-20mA 16 Bit, S.E. (without 753-474 1
1)
Data format for S5 control with FB 251
Accessories
Item No.
Pack.
Unit
753 Series Connectors
753-110 25
Coding elements 753-150 100
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Also see "Approvals Overview" in Section 1
Conformity marking 1
Shipbuilding (versions upon
request)
ABS, BV, DNV, GL, KR, LR*, NKK*, PRS*, RINA*
*753 Series, pending
r UL 508
r ANSI/ISA 12.12.01
Class I, Div. 2, Grp. ABCD, T4
4 IEC 60079-0, -15
BR-Ex nA II T4
750-472, -474
4 EN 60079-0, -15
EN 61241-0, -1
I M2 / II 3 GD Ex nA IIC T4
Technical Data
Number of inputs 2
Power supply via system voltage DC/DC
Current consumption (internal) 75 mA
Input voltage (max.) 24V
Input voltage non-linear, overload protected
V = 1.2 V + 100 Ω x I meas.
Signal current 0 - 20mA (750-472, 753-472)
4 - 20mA (750-474, 753-474)
Input resistance 220Ω / 20mA
Overvoltage protection 30 V polarity reversal protection
Resolution 15 bits
Conversion time (typ.) 80 ms
Input filter 50Hz
Noise rejection at sampling frequency < -100 dB
Noise rejection above sampling frequency < -40 dB
Measuring error (25°C) < ± 0.1 % of the full scale value
Temperature coefficient < ± 0.01 % / K of the full scale value
Isolation 500 V system/supply
Bit width 2 x 16 bits data
2 x 8 bits control/status (optional)
Wire connection CAGE CLAMP
®
Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped lengths, 750/753 Series 8 ... 9 mm / 0.33 in
9 ... 10 mm / 0.37 in
Width 12 mm
Weight 55.5 g
EMC: 1 - immunity to interference acc. to EN 61000-6-2 (2005)
EMC: 1 - emission of interference acc. to EN 61000-6-4 (2007)
EMC: marine applications
- immunity to interference acc. to Germanischer Lloyd (2003)
EMC: marine applications
- emission of interference acc. to Germanischer Lloyd (2003)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 18.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com