Datasheet
750-342
1
112
ETHERNET TCP/IP Fieldbus Coupler
10 Mbit/s; digital and analog signals
Data contacts
Fieldbus
connection
RJ-45
Power jumper contacts
0 V
Supply via
power jumper contacts
24 V
Supply
24 V
0 V
Status
voltage supply
-System
-Power jumper contacts
Configuration
interface
24V
0V
+
+
— —
01 02
ON
LINK
TxD/RxD
I/O
ETHERNET
C
D
B
A
ERROR
750-342
W
The ETHERNET TCP/IP fieldbus coupler supports a number of network proto-
cols to send process data via ETHERNET TCP/IP. By observing the relevant IT
standards, connection to existing local or global networks (LAN, Internet) is
possible without any problem.
Using ETHERNET as a fieldbus makes universal data transmission between the
factory and the office possible. Moreover, the ETHERNET TCP/IP fieldbus
coupler offers remote maintenance, i.e. processes can be controlled regardless
of the location.
Process data exchange is done using the MODBUS/TCP protocol. The
buscoupler supports all I/O modules and automatically configures, creating a
local process image.
The HTML pages that are stored in the fieldbus coupler allow access to infor-
mation on configuration, status, or I/O data of the ETHERNET TCP/IP fieldbus
coupler. Only a standard WEB browser is required.
Dynamic configuration of the IP addresses via a BootP server provides a flexible
and easy way to configure the network.
Description
Item No.
Pack.
Unit
ETHERNET TCP/IP 10 MBit 750-342 1
Accessories
Item No.
Pack.
Unit
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Also see "Approvals Overview" in Section 1
Conformity marking 1
Shipbuilding ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA
r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
4 IEC 60079-0, -15 BR-Ex nA II T4
4 EN 60079-0, -15
EN 61241-0, -1
I M2 / II 3 GD Ex nA IIC T4
System Data
No. of couplers connected to Master limited by ETHERNET specification
Transmission medium Twisted Pair S-UTP 100 Ω cat. 5
Max. length of fieldbus segment 100 m between hub station and 750-342;
max. length of network limited by
ETHERNET specification
Baud rate 10 Mbit/s
Buscoupler connection RJ-45
Protocols MODBUS/TCP, HTTP, BootP,
MODBUS/UDP
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 16.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com