Datasheet

24V 0V
++
——
PE PE
01 02
750-324
READY
BA
RC
I/O RUN
INTERBUS-S
C
D
B
A
RD
I/O ERR
WAGO Kontakttechnik GmbH Postfach 2880D-32385 Minden Tel.: 05 71/887-0 E-Mail: info@wago.com
Hansastr. 27 D-32423 Minden Fax.: 05 71/887-169 Web: http://www.wago.com
INTERBUS
Fieldbus Coupler
; EN 50254; 500 kbaud; digital signals
Max. no. of nodes 256
Max. no. of I/O points 4096 (depends on master)
Transmission medium certified Cu cable
Max. length of fieldbus segment 400 m
Baud rate 500 kbaud
Transmission time typ. 1.43ms
(10 nodes; 32 Is, 32 Os per node)
Buscoupler connection 1 x D-SUB 9; plug for input interface
1 x D-SUB 9; socket for output interface
This buscoupler allows connection of the
WAGO I/OSYSTEM as a slave to the INTERBUS field-
bus.
The buscoupler is capable of supporting all digital bus
modules and automatically configures, creating a local pro-
cess image.
INTERBUS allows the storing of the process image in the
corresponding Master control (PLC, PC or NC).
The local process image is divided into two data zones
containing the data received and the data to be sent.
The process data can be sent via the INTERBUS fieldbus to
the PLC, PC or NC for further processing, and received
from the field via INTERBUS.
The data of the modules is stored in the process image
which is created automatically according to the order in
which the modules are connected to the buscoupler. The
bits of the digital modules are sent byte by byte. If the
amount of digital information exceeds 8 bits, the buscoup-
ler automatically starts with a new byte.
System Data
750-324 1
Item-No. Pack.-unit
pcs
INTERBUS/Digital
Description
UL E175199, UL508
UL E198726, UL1604
Class I Div2 ABCD T4A
KEMA 01ATEX1024 X
EEx nA II T4
Standard EN 50254
Certification INTERBUS CLUB
Conformity marking 1
Standards and Approvals
INTERBUS files 750-913
Miniature WSB quick marking system pages 1.166 /167
Accessories
Status
voltage supply
-Power jumper
contacts
-System
Data contacts
Supply
24 V
0 V
Supply via
power jumper
contacts
24 V
0 V
Power jumper
contacts
Fieldbus
connection
D-Sub
Input
Fieldbus
connection
D-Sub
Output
Configuration
interface
Subject to design changes