Data Sheet
Data sheet | Item number:288-414
Relay module with driven contacts; Nominal input voltage: 24 V AC/DC; 4
break and 4 make contacts; Limiting continuous current: 6 A; Module width:
64 mm
www.wago.com/288-414
06.12.2018Page /1 4
Color:
Item description
Note:
If required a ventilation hole (e) can be made in the cover, reducing the degree of protection from IP67 to IP30.
If an outer contact (20) should weld then the forced operated inner contact (12) driven by the actuator (d) remains open. The rotating armature (c)
remains free to move. The unaffected contact pairs can operate normally, (i. e. their function to make or break remains unaffected).
If an inner contact should weld (12) then the movement of the rotating armature (c) is blocked via the operator (d). Open contacts of all four contact
pairs remain open. This arrangement corresponds to conventional, forced contact operation.
Data
Technical Data
Control circuit
Nominal input voltage U
N
24 V AC/DC
Input voltage range -15 … +10 %
Nominal input current at U
N
26 mA