Datasheet
3
139
INTERFACE ELECTRONIC
▯ = ON
2857-534Einstellmöglichkeiten DIP-Schalter
Default-Einstellungen
Kaltstellenkompensation ON
Sensorart Thermoelement Typ J
Startwert 0 °C
Endwert 1000 °C
Hysterese 3 K
Anzugs-/Abfallverzögerung
Relais/Digitalausgang DO
0 s
DIP-Schalter S1
Sensorart
Thermoelement
Kaltstellenkompensation Hysterese
Anzugs-/Abfallverzögerung
Relais/Digitalausgang DO
1234 Typ 5 6 T /
K 789
t / s
10
Nicht belegt
JON 3 0
● K ● OFF ● 5 ● 1
●E ●2
●● R ●● 3
●N ●4
●● S ●● 5
●● T ●● 8
●●● B ●●● 10
●C
DIP-Schalter S2
Startwert Endwert
12345
Temperatur / °C 6789
10
Temperatur / °C
0 1000
● OFF ● OFF
● -200 ● -200
● ● -150 ● ● -150
● -100 ● -100
● ● -50 ● ● -50
● ● 50 ● ● 50
● ● ● 100 ● ● ● 100
● 150 ● 150
● ● 200 ● ● 200
● ● 250 ● ● 250
● ● ● 300 ● ● ● 300
● ● 350 ● ● 350
● ● ● 400 ● ● ● 400
● ● ● 450 ● ● ● 450
●●●● 500 ●●●● 500
● 550 ● 550
● ● 600 ● ● 600
● ● 650 ● ● 650
● ● ● 700 ● ● ● 700
● ● 750 ● ● 750
● ● ● 800 ● ● ● 800
● ● ● 850 ● ● ● 850
● ● ● ● 900 ● ● ● ● 900
● ● 950 ● ● 950
● ● ● 1000 ● ● ● 1000
● ● ● 1050 ● ● ● 1050
● ● ● ● 1100 ● ● ● ● 1100
● ● ● 1150 ● ● ● 1150
● ● ● ● 1200 ● ● ● ● 1200
●●●● 1300 ● ● ● ● 1300
●●●●● 1400 ● ● ● ● ● 1400