HEAT DISPERSAL
The inverter generates heat while it is working. This is not a malfunction. However,
if the inverter gets too hot while working, it will turn off by itself. Position the
inverter where air flows freely around it to allow the heat to disperse. The inverter’s
thermal protection prevents it from operating when its temperature exceeds
130ºF ± 10ºF.
TROUBLESHOOTING
PROBLEM: Low or No Output Voltage – Fault LED Lit
Reason Solution
Poor contact with battery or inverter
terminals.
Clean terminals thoroughly. Reinstall
and tighten.
PROBLEM: Inverter Automatically Shut Down – Fault LED Lit
Reason Solution
Battery voltage below 10V Charge or replace battery.
Inverter is too hot.
(Thermal protection mode.)
Allow inverter to cool.
Check for adequate ventilation.
Reduce the load on the inverter to
rated continuous power output.
Unit may be defective. See warranty and call customer service.
Equipment being operated draws too
much power.
Use a higher capacity inverter or do
not use this equipment.
PROBLEM: Pulsing Alarm
Reason Solution
Input voltage below 10.5V Keep input voltage above 10.5V
Poor or weak battery condition. Recharge or replace battery.
Poor or loose cable connection. Inspect terminals and tighten all
connections.
Inadequate power being delivered to
the inverter or excessive voltage drop.
Use heavier gauge DC cable.
Keep cable length as short as possible.