2.9 Ground Fault Circuit Interrupter (GFCI)
See Graphic: wc_gr003143
The GFCI should be tested for proper operations every time the
generator is used.
Normal operating state - sensing device green LED is “ON” and circuit
breaker is at “ON” position.
2.9.1 Press “TEST” button (g). Green LED should go “OUT” and red LED
should come “ON” and circuit breaker should trigger to “OFF” position
(d).
2.9.2 If sensing device LED or breaker does not trip or change state, “DO
NOT USE”. Consult an electrician for assistance.
2.9.3 Press “RESET” button (h). Red LED should turn “OFF” and green LED
should turn “ON”.
2.9.4 Manually reset (switch) circuit breaker to “ON” position to restore
circuit power (d).
2.10 Twist-Lock Receptacles
See Graphic: wc_gr003143
Twist-lock receptacles (c, j) are used at the 120V Amp and 120/240V
outlets. These receptacles are protected by the GFCI.
To attach a power cord to a twist-lock receptacle, insert plug into
receptacle and turn it clockwise to lock it in place.