Operator`s manual
Operation G 25
50 wc_tx001045gb.fm
4.21 Current Overload Fault
Along with engine functions, the ECM continuously monitors the
current load in each phase. The values for current overload are
programmed into the ECM at the factory and are different for each
generator size.
4.21.1 When an overcurrent condition is sensed in any leg, the warning/fault
LED (d) will flash and the display will indicate OVERCURRENT.
4.21.2 If the overcurrent condition persists, the main circuit breaker (a) will
open and the display will change to OVRLOAD - SET BRKR. This
indicates an overload fault.
4.21.3 To clear the overload fault, reset the main circuit breaker. Failing to
reset the main circuit breaker will cause the machine to shut down
after 5 minutes. The display will then change to OVERLOAD.
4.22 Event Log
The control module contains an event log that records the first and
last occurrences of pre-alarms and alarms. See Using the LCD and
Keypad for instructions on how to access the event log.