Operator`s manual
G 25 Operation
wc_tx001045gb.fm 41
4.11 Convenience Receptacles
See Graphic: wc_gr005864
The generator is equipped with one 120V/240V twist lock receptacle
(m) rated at 30A, and one 120V/240V twist lock receptacle (l) rated at
50A. The two 120V duplex receptacles (n) are equipped with ground
fault interrupts (GFI). Receptacles do not connect through the main
line circuit breaker. Each receptacle is protected by its own circuit
breaker (k) which is located directly above it. Power to the receptacles
is available any time the generator engine is running, even with the
main line circuit breaker open.
Note: For the G25, when the voltage selector switch is in the 480V/3Ø
position, voltage at the duplex receptacles is 139V, and voltage at the
30/50A receptacles is 139/240V. When the voltage selector switch is
in the 208V/3Ø position, voltage at the 30/50A receptacles is 120/
208V. When the voltage selector switch is in the 208V/3Ø position, the
voltage can be adjusted with the voltage adjustment rheostat (f) to
240V/3Ø. The voltage at the duplex receptacles is 139V, and voltage
at the 30/50A receptacles is 139/240V.
4.12 Remote Run Terminal Block
See Graphic: wc_gr005864
The remote run terminal block (o) is located just to the right of the twist-
lock receptacles. It provides connection points for installation of a
remote start switch. When it is connected to a transfer switch, it allows
the generator to be used as a standby power supply.
4.13 Panel Door Interlock Switch
See Graphic: wc_gr005864
The customer connection lugs panel access door is equipped with an
interlock switch (q). When the door is opened this switch
automatically trips the main circuit breaker. Voltage to the receptacles
will not be cut.