PUREHEAT™ HYDRONIC AIR HEATER OPERATOR’S MANUAL – SECTION 4
4- 6 © 2006 Ground Heaters, Inc. V. 2, Rev. 09/01/06
4.5 SUMMER STORAGE INSTRUCTIONS
1. Allow the heater to cool sufficiently. Cover the chimney and the Burner with plastic wrap or other
waterproof material. This will prevent corrosive moisture build-up and blockages caused by animal
nests. Burners not installed should be stored in a cool, dry place.
2. Remove emergency break-away battery and store the battery in a cool, dry place. Connect the
battery to a trickle charger once every 30 days to maintain full charge.
3. Perform a thorough inspection for leaks, and correct. Double-check that all valves are shut.
4. Ensure all manifold Quick-Connect covers are in place and secured.
5. Shut and lock all doors.
6. Protect the tires from direct sunlight if stored outdoors.
NOTE: Do not drain the HTF. The heater and plumbing must remain flooded with HTF to prevent
corrosion (rusting).
4.6 PRE-SEASON MAINTENANCE
(Refer to Section 3 of the Service Manual for detailed instructions.)
1. Remove all waterproof wrapping or covering from the chimney and Burner.
2. Test and reinstall emergency break-away battery.
3. Remove the Flue Access Door to inspect the Hydronic Heater Interior and fire tubes. Clean out any
soot or flaked material. Remount the Flue Access Door.
For Oil Burners
: Remove the Burner electrode assembly. Replace the nozzle with an exact
replacement. Adjust or replace the electrodes as necessary.
4. Remove the Burner to inspect and clean the flame head.
5. Replace fuel filter element.
6. Reinstall the electrode assembly and verify the “Z” distance is correctly set.
7. Remount Burner using a new Burner mounting gasket.
8. Adjust Burner settings as directed in Section 3, BURNER ADJUSTMENT AND SHUTDOWN.
9. Verify HTF level.