Operator`s manual
PUREHEAT™ HYDRONIC AIR HEATER OPERATOR’S MANUAL–SECTION 2
V. 2, Rev. 09/01/06 © 2006 Ground Heaters, Inc. 2- 1
START UP, OPERATION AND SHUTDOWN
2.1 CIRCULATION SYSTEM ADVISORY
2.1.1 Standard Configuration Performance
2.1.1.1 HX200 Heat Xchangers™
A Pureheat™ Hydronic Air Heater equipped with HX200 Heat Xchangers
TM
should conform to the
following system configurations:
• Connection of up to Four (4) HX200 Heat Xchangers
TM
utilizing any combination [50 ft (15 m),
100 ft (30 m) or 200 ft (61 m)] of Circulation Hoses. Maximum run should not exceed 200 ft (61
m) from base unit.
• The maximum vertical rise or drop from the Pureheat to each HX200 is 60 ft (18 m) one way from
base unit.
2.1.1.2 HX200 Heat Xchangers™ with Optional Booster Pump
A Pureheat™ Hydronic Air Heater equipped with HX200 Heat Xchangers™, optional Booster Pump and
Auxiliary Pump Panel should conform to the following system configurations:
• Connection of up to Four (4) HX200 Heat Xchangers
TM
utilizing any combination [50 ft (15 m),
100 ft (30 m) or 200 ft (61 m)] of Circulation Hoses with a maximum overall horizontal run not to
exceed 400 ft (122 m) from base unit.
• The maximum vertical rise or drop from the Pureheat to each HX200 is 100 ft (30 m) one way
from base unit.
2.1.1.3 HX100 Heat Xchangers™
A Pureheat™ Air Heater equipped with HX100 Heat Xchangers
TM
and 4-Port Remote Manifolds should
conform to the following system configurations:
• Connect the Four (4) 4-Port Remote Manifolds utilizing any combination [50 ft (15 m) or 100 ft (30
m)] of Circulation Hoses with a maximum overall horizontal run not to exceed 150 ft (45 m) for
each 4-Port Remote Manifold.
• The maximum vertical rise or drop from the Pureheat to each Xchanger
TM
or 4-Port Remote
Manifold is 60 ft (18 m) one way from base unit.
• Connect Two (2) HX100 Heat Xchangers
TM
to each of the Four (4) 4-Port Remote Manifolds
utilizing the 40 ft (12 m) 5/8 in. ID Black Circulation Hoses mounted on the HX100 Heat
Xchangers
TM
.
2.1.1.4 HX100 Heat Xchangers™ with Booster Pump
A Pureheat™ Hydronic Air Heater equipped with the HX100 Heat Xchangers™, 4-Port Remote
Manifolds, optional Booster Pump and Auxiliary Pump Panel should conform to the following system
configurations:
• Connect the Four (4) 4-Port Remote Manifolds utilizing any combination [50 ft (15 m), 100 ft (30
m) or 200 ft (61 m)] of Circulation Hoses with a maximum overall horizontal run not to exceed 350
ft (106 m) for each 4-Port Remote Manifold.
• The maximum vertical rise or drop from the Pureheat to each Xchanger or 4-Port Remote
Manifold is 100 ft (30 m) one way from base unit.
• Connect Two (2) HX100 Heat Xchangers
TM
to each of the Four (4) 4-Port Remote Manifolds
utilizing the 40 ft (12 m) 5/8 in. ID Black Circulation Hoses mounted on the HX100 Heat
Xchangers
TM
.