PUREHEAT™ HYDRONIC AIR HEATER OPERATOR’S MANUAL–SECTION 2
V. 2, Rev. 09/01/06 © 2006 Ground Heaters, Inc. 2- 1
START UP, OPERATION AND SHUTDOWN
2.1 CIRCULATION SYSTEM ADVISORY
2.1.1 Standard Configuration Performance
2.1.1.1 HX200 Heat Xchangers™
A Pureheat™ Hydronic Air Heater equipped with HX200 Heat Xchangers
TM
should conform to the
following system configurations:
Connection of up to Four (4) HX200 Heat Xchangers
TM
utilizing any combination [50 ft (15 m),
100 ft (30 m) or 200 ft (61 m)] of Circulation Hoses. Maximum run should not exceed 200 ft (61
m) from base unit.
The maximum vertical rise or drop from the Pureheat to each HX200 is 60 ft (18 m) one way from
base unit.
2.1.1.2 HX200 Heat Xchangers™ with Optional Booster Pump
A Pureheat™ Hydronic Air Heater equipped with HX200 Heat Xchangers™, optional Booster Pump and
Auxiliary Pump Panel should conform to the following system configurations:
Connection of up to Four (4) HX200 Heat Xchangers
TM
utilizing any combination [50 ft (15 m),
100 ft (30 m) or 200 ft (61 m)] of Circulation Hoses with a maximum overall horizontal run not to
exceed 400 ft (122 m) from base unit.
The maximum vertical rise or drop from the Pureheat to each HX200 is 100 ft (30 m) one way
from base unit.
2.1.1.3 HX100 Heat Xchangers™
A Pureheat™ Air Heater equipped with HX100 Heat Xchangers
TM
and 4-Port Remote Manifolds should
conform to the following system configurations:
Connect the Four (4) 4-Port Remote Manifolds utilizing any combination [50 ft (15 m) or 100 ft (30
m)] of Circulation Hoses with a maximum overall horizontal run not to exceed 150 ft (45 m) for
each 4-Port Remote Manifold.
The maximum vertical rise or drop from the Pureheat to each Xchanger
TM
or 4-Port Remote
Manifold is 60 ft (18 m) one way from base unit.
Connect Two (2) HX100 Heat Xchangers
TM
to each of the Four (4) 4-Port Remote Manifolds
utilizing the 40 ft (12 m) 5/8 in. ID Black Circulation Hoses mounted on the HX100 Heat
Xchangers
TM
.
2.1.1.4 HX100 Heat Xchangers™ with Booster Pump
A Pureheat™ Hydronic Air Heater equipped with the HX100 Heat Xchangers™, 4-Port Remote
Manifolds, optional Booster Pump and Auxiliary Pump Panel should conform to the following system
configurations:
Connect the Four (4) 4-Port Remote Manifolds utilizing any combination [50 ft (15 m), 100 ft (30
m) or 200 ft (61 m)] of Circulation Hoses with a maximum overall horizontal run not to exceed 350
ft (106 m) for each 4-Port Remote Manifold.
The maximum vertical rise or drop from the Pureheat to each Xchanger or 4-Port Remote
Manifold is 100 ft (30 m) one way from base unit.
Connect Two (2) HX100 Heat Xchangers
TM
to each of the Four (4) 4-Port Remote Manifolds
utilizing the 40 ft (12 m) 5/8 in. ID Black Circulation Hoses mounted on the HX100 Heat
Xchangers
TM
.