Technical data
73
W&T
Subject to errors and modifications
After you have entered all the parameters, confirm by clicking
on the Temporary Storage button.
From the navigation tree select: Config >> Ports >> Port 1 >>
Output Mode.
Here you select the analog output as Binary 1 which you want
to be controlled by Modbus. Confirm by clicking on the
Temporary Storage button.
Now you must still enable the new settings. Use the Logout
button or menu sequence Config >> Session Control >> LogOut.
After clicking on the Save button all the settings are updated in
the Web-IO and the start page is reconstructed. The Web-IO can
now be accessed by the Modbus client.