Technical data
48
W&T
Server HTTP Port
Is only relevant for Box2Box mode and specifies the HTTP port
on which a control line should open a connection to the slave
box.
Unless otherwise specified, always use Port 80 here.
Server IP Addr
Enter here the IP address of the server.
Server Password
A server password only needs to be entered if the Web-IO is
used as a Box-to-Box Master or needs to access a different Web-
IO as a TCP client in Server mode. More about this in the Box-
to-Box section.
Inactive Timeout
Here a timer is configured. After the time expires, the Web-IO
closes the TCP connection. The value is entered in decimal and
in 100ms increments. The timer is reset during an active
connection when data are exchanged.
Example: The value 10 corresponds to one second. If no data
transfer is detected for one second, the Web-IO closes the
connection.
If no value is entered, automatic connection closing is
disabled..
Binary Trigger
Here you select the ports whose status change should act as a
trigger for opening the TCP connection and sending data to the
server (important for event-triggered applications).
Interval
If you want the status of the inputs to be sent cyclically to the
server application, you can enter here the interval in 100ms
increments.
Example: A value of 300 corresponds to 30 seconds.