Technical data
133
W&T
Subject to errors and modifications
enable“ under „Config >> Device >> Basic Settings >>
HTTP“.
4.3 Polling via SNMP
The input/output can be directly polled or set using SNMP Get
instructions. Reach the respective port using the following
paths:
<IP-Adresse> 1.3.6.1.4.1.5040.1.2.28.1.3.1.1.1 = Output value
1 as Octet String (Read/Write).
<IP-Adresse> 1.3.6.1.4.1.5040.1.2.28.1.4.1.1.1 = Output value
as integer value in thousandths, not comma delineated (Read/
Write).
<IP-Adresse> 1.3.6.1.4.1.5040.1.2.28.1.3.1.1.2 = Output value
2 as Octet String (Read/Write).
<IP-Adresse> 1.3.6.1.4.1.5040.1.2.28.1.4.1.1.2 = Output value
2 as integer value in thousandths, not comma
delineated.(Read/Write).
The IDs for the various device versions are as follows:
#57661: 1.3.6.1.4.1.5040.1.2.28...
#57662: 1.3.6.1.4.1.5040.1.2.29...
!
Specify the configured SNMP Read or Read/Write
Community for polling.
An MIB for incorporation into management applications can be
found on the datasheet page for the device at the WuT
homepage http://www.wut.de (download). You can also find the
MIB file in the device itself. It can be downloaded from the
following address:
http://<ip address>/mib.zip