Technical data

Prod. No.: 57612, 57613
Thermo-H
yg
ro Probe: I2C connection
Air
p
ressure
p
robe: SPI connection
Network: 10/100BaseT autosensin
g
Su
pp
l
y
volta
g
e:
57612: 12-24V AC / DC using screw terminal
57613: Power-over-Ethernet (PoE) or via screw terminal with DC
24V .. 48V (+/-10%) or AC 18Veff .. 30Veff (+/-10%)
Measurin
g
unit
Measurin
g
ran
g
e: -40°C...85°C
,
0..100% rF
,
10-1100 hPa
Resolution: 1/10 °C
,
1/10% rF
,
0.1 hPa
Measurin
g
error: ±2% Kelvin
,
±2.5% abs ±2% rel.rF
,
± 2hP
a
Stora
g
e fre
q
uenc
y
:1
,
5
,
15
,
60 min
Memor
y
de
p
th (832kB): min. 10 weeks
,
max. 8
y
ears
Other data
Galvanic isolation: Measurement in
p
uts to network: min. 500
V
E-mail function: Mail for sendin
g
alarms or as re
p
ortin
g
function
DC 12V .. 48V (+/-10%)
AC 9Veff (-5%) - 24Veff (+5%)
AVG: 200mA @12VDC, 100mA @24VDC, 100mA @20VAC
Max: 240mA @12VDC
PoE Class 1 (0.44 - 3.84W)
Configuration interface: RS232 serial port, 9600 baud, 8 data bits, 1 stop bit, no
p
arit
y
Housin
g
: Plastic com
p
act housin
g,
105x75x22mm
Wei
g
ht: a
pp
rox. 200
g
Ambient stora
g
e tem
p
erature: -40..+70°C
Ambient operating temperature: 0 .. +60°C
Current consumption:
Supply voltage: