User Manual

Table Of Contents
Sonik G2BT Base Transmitter User Manual
March 14, 2002 63 7M487C4
lostACPwr This alarm triggers when the
AC power is lost and the
system is running off the
battery.
Critic
al
This alarm clears when the AC
power is online.
g2btFail This alarm triggers when the
G2BT fails.
Critic
al
This alarm clears when the
G2BT is working properly.
parmsNotSaved This alarm triggers when the
user ADMIN logs off without
saving the system
configuration to FLASH
memory.
Info This alarm clears when the
saveParms command is issued
or when user ADMIN saves
the system configuration to
FLASH when terminating the
user session.
powerControlFail This alarm triggers when the
system is unable to control
excessive power output or
temperature using cutbacks.
Critic
al
This alarm clears when the
system can control excessive
power output or temperature.
reset This alarm triggers on system
startup. As the alarm
management software is
initialized two RESET alarm
events are generated. The first
event is a CLEAR event that
issues a SNMP trap message
containing the value of 9999
for the
alarmIndex
indicating
that all outstanding alarm
conditions should be reset. The
second event is a SET event
and operates as configured
using the ALARM RESET
command.
Major This alarm is not automatically
cleared by the system and can
only be manually cleared by
the operator.
resetPending This alarm triggers when an
operator enters the RESET
command.
Major The alarm status is CLEAR
upon reset. Since it never
transitions from SET to
CLEAR status no
corresponding console/SNMP
messages or log entries are
generated for the CLEAR
event.
statsLogFull This alarm triggers when the
statistics log is full.
Major This alarm clears when one or
more entries in the stats log is
cleared.
tempHigh This alarm triggers when the
temperature inside the station
cabinet exceeds the high
temperature threshold.
Major This alarm clears when the
temperature inside the station
cabinet falls below the high
temperature threshold.
tempLow This alarm triggers when the
temperature inside the station
cabinet falls below the low
temperature threshold.
Major This alarms clears when the
temperature inside the station
cabinet rises above the low
temperature threshold.