User Manual

Table Of Contents
RF-Baton! Transmitter Controller Installation and Operation Maintenance
June 1999 6880497G01-B 6-21
Verify Proper Control Message Output
Verify the control commands generated by the RF-B! transmitter controller. The primary
concern for this procedure is that the proper protocol format is recognized.
For ReFLEX paging systems, there are few control commands necessary, while the InFLEXion
protocol requires many control commands to be transmitted.
1. Connect your FIPS terminal to the FIPS Serial Port on the front panel of the RF-B!
transmitter controller and log into the FIPS session (see Chapter 5, "Operation",
paragraph, "Service Terminal").
2. Enable the Page Control Launch Manager (PCLM) command trace.
At the prompt, type:
a 192 PCLM 1 <Enter>
The terminal displays the PCLM 1 trace.
a. If the system is a ReFLEX system, the paging batches are expected to be continuous
with relatively far fewer control commands than an InFLEXion system. For
example:
==batch is contiguous
No freq chng
offset freq & mod type match
==batch is contiguous
No freq chng
offset freq & mod type match