Preinstallation RF-Orchestra!™ Transmitter Installation and Operation
3-2 6880493G02-C July 2000
The minimum door dimensions should be 36 in. (91.44 cm) wide by 84 in. (213.36 cm)
high.
All exterior doors should have tamper-proof locks installed for security.
The interior site environment must be maintained between -30 ˚C and +60 ˚C (-22 ˚F and
+140 ˚F).
Proper surge protection is required for all antennas, data circuits, and power inputs to
prevent potential damage to the site equipment.
Equipment Cabinets
One cabinet is offered for the RF-O! paging station. The dimensions and racking information
follow (see Table 3-1).
Cabinet Spacing
During installation, allow at least two feet of space in front of and behind each cabinet to
allow access to the cabinet for servicing and adequate air flow into and out of the equipment
(see Figure 3-2).
CAUTION
This equipment is not approved or recommended for outdoor use.
Table 3-1: Cabinet and Rack Dimensions
Cabinet Width Depth Height
Configuration
(rack units)
X128
23.31 in.
59.21 cm
27.68 in.
70.31 cm
83.50 in.
212.09 cm
43