Specifications
·
If the channels specified are not on a Frequency/Totalize SCP, an error will be
generated.
·
Related Commands: SENS:TOT:RESET:MODE, INPUT:POLARITY
·
*RST Condition: SENS:FUNC:COND and INP:POL NORM for all digital SCP
channels.
Usage SENS:FUNC:TOT (@148) channel 48 is a totalizer
[SENSe:]FUNCtion:VOLTage[:DC]
[SENSe:]FUNCtion:VOLTage[:DC] [<range>,](@<ch_list>) links the specified
channels to return dc voltage.
Parameters
Parameter
Name
Parameter
Type
Range of
Values
Default
Units
range numeric (float32) see comments V dc
ch_list channel list (string) 100 - 163 none
Comments
·
The <range> parameter: The VT1419A has five ranges: 0.0625 V dc, 0.25 V dc,
1Vdc,4Vdcand16Vdc. Toselect a range, simply specify the range value (for
example, 4 selects the4Vdcrange). If a value is specified larger than one of the
first four ranges, the VT1419A selects the next higher range (for example, 4.1
selects the 16 V dc range). Specifying a value larger than 16 causes an error.
Specifying 0 selects the lowest range (0.0625 V dc). Specifying AUTO selects
auto range. The default range (no range parameter specified) is auto range.
·
If using amplifier SCPs, set them first and keep their settings in mind when
specifying a range setting. For instance, if expected signal voltage is to be
approximately 0.1 V dc and the amplifier SCP for that channel has a gain of 8,
<range> must be set no lower than 1V dc or an input out-of-range condition will
exist.
·
The *CAL? command calibrates channels based on Sense Amplifier SCP setup at
the time of execution. If SCP settings are changed, those channels are no longer
calibrated. *CAL? must be executed again.
·
See “Linking Input Channels to EU Conversion” on page 57 for more
information.
·
When Accepted: Not while INITiated
·
Related Commands: *CAL?, INPUT:GAIN¼
·
*RST Condition: SENSE:FUNC:VOLT AUTO,(@100:163)
VT1419A Command Reference
[SENSe]
276 Chapter 6