Specifications
Usage program must put table constants into array table_block
DIAG:CUST:PIEC 1,table_block,(@100:107) send characterized thermocouple table for
use by channels 0-7
SENS:FUNC:CUST:TC N,.25,(@100:107) link custom thermocouple EU with chs 0-7,
use reference temperature compensation for
N type wire.
SENSE:REF RTD,92,(@120) designate a channel to measure the
reference junction temperature
include these channels in a scan list (REF channel first)
INITiate then TRIGger module
[SENSe:]FUNCtion:FREQuency
[SENSe:]FUNCtion:FREQuency <ch_list> sets the SENSe function to frequency
for channels in <ch_list>. Also configures the channels specified as digital inputs.
Parameters
Parameter
Name
Parameter
Type
Range of
Values
Default
Units
ch_list string 132 - 163 none
Comments
·
If the channels specified are on an SCP that doesn’t support this function, an error
will be generated. See the SCP’s User’s Manual for its capabilities.
· Use the SENSe:FREQuency:APERture command to set the gate time for the
frequency measurement.
·
Related commands: SENS:FREQ:APER
·
*RST Condition: SENS:FUNC:COND and INP:POL NORM for all digital SCP
channels
Usage SENS:FUNC:FREQ (@144) set channel 44’s sense function to frequency
[SENSe:]FUNCtion:RESistance
[SENSe:]FUNCtion:RESistance <excite_current>,[<range>,](@<ch_list>) links
the EU conversion type for resistance and range with the channels specified by
<ch_list>.
Parameters
Parameter
Name
Parameter
Type
Range of
Values
Default
Units
excite_current discrete(string) 30E-6 | 488E-6 | MIN | MAX Amps
range numeric (float32) see first comment V dc
ch_list channel list (string) 100 - 163 none
Comments
·
The <range> parameter: The VT1419A has five ranges: 0.0625 V dc, 0.25 V dc,
1 V dc, 4 V dc, and 16 V dc. To select a range, simply specify the range value
VT1419A Command Reference
[SENSe]
Chapter 6 271