Specifications
– 6 –
LOCATION - ALL MODELS
The equipment area must be kept free and clear of combustible substances. The broiler, when installed,
must have minimum clearance from combustible and noncombustible construction of:
Models Minimum Clearance to Combustible Construction
GHCBO40, GHCB44 & GHMCB44 . . . . . . . . 6" (152.4 mm) sides and rear
IR44 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0" sides and 4" (101.6 mm) rear
GHCB1 & GHCB2 . . . . . . . . . . . . . . . . . . . . . . 4" (101.6 mm) sides and rear
IR2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0" sides and 4" (101.6 mm) rear
The installation location must allow adequate clearances for servicing and proper operation. A minimum
front clearance of 48" (121.9 cm) is required.
The broiler must be installed so that the flow of combustion and ventilation air will not be obstructed.
Adequate clearance for air openings into the combustion chamber must be provided. Make sure there
is an adequate supply of air in the room suitable for the amount of combustion gas feeding the broiler
burners.
INSTALLATION CODES AND STANDARDS - ALL BROILER MODELS
Install this equipment in accordance with:
In the United States
1. State and local codes, or in the absence of local codes, with:
2. National Fuel Gas Code, ANSI-Z223.1 (latest edition), available from the American Gas Association,
Inc., 1515 Wilson Blvd., Arlington, VA 22209.
3. National Electrical Code ANSI/NFPA70 (latest edition) (if applicable).
In Canada
1. Local codes.
2. CSA Standard C22.2 No. 3 Electrical Features of Fuel Burning Equipment (latest edition).
3. CAN/CGA-B149.1 National Fuel Gas Code (latest edition), available from The Canadian Gas
Association, 178 Rexdale Rd., Etobicoke, Ontario, Canada M9W 1R3.
For an appliance equipped with casters, instructions that (1) the installation shall be made with a
connector that complies with the Standard for
Connectors for Movable Gas Appliances, ANSI Z21.69
or
Connectors for Moveable Gas Appliances, CAN/CGA-6.16
, and a quick-disconnect device that
complies with the Standard for
Quick-Disconnect Devices for Use With Gas Fuel, ANSI Z21.41
or
Quick Disconnect Devices for Use with Gas Fuel, CAN1-6.9
, (2) adequate means must be provided
to limit the movement of the appliance.