Instruction Manual

VTS reserves the right to implement changes without prior notice.
www.vtsgroup.com Page 7 of 16 ver. 2.0 (11.2021)
whereas the concentration value can be calculated basing on the voltage value form using
the following formula:
OUT
RANGE
V
VOLTAGE
humiditylative
%100
_Re
where:
VOLTAGERANGE = 5V or 10V (0-5V or 0-10V set on the configuration DIP-switch 2
see section 3.4)
Exemplary values are shown in the table below:
Relative humidity
[%]
Voltage range = 5 V
Voltage range = 10V
0
0.0V~
0.0V~
25
1.0V~
2.0V~
50
2.5V
5.0V
75
3.75V~
7.5V~
100
5.0V~
10.0V~
3.4. Configuration of MODBUS bus, serial port and analogue output
The purpose of the consecutive switches of the left DIP-switch is as follows (default values are in
bold)
0 OFF 1 ON CONFIGURATION ADDRESS