Instruction Manual
VTS reserves the right to implement changes without prior notice.
www.vtsgroup.com Page 4 of 16 ver. 2.0 (11.2021)
Response time
1)
8 s
1) The prerequisite for obtaining the given response times is an air flow > 1m/s; the response time
indicated is equal to one time constant corresponding to 63 % of the steady value
2.3. Parameters of temperatures measurement
Sensor model
SHT31-DIS-B
Measurement range
0ºC ÷ 90ºC
Resolution
14.5 bit (0.01ºC)
Measurement accuracy (over entire measuring range)
± 0.25ºC
Sampling frequency
1 Hz
Response time
1)
2 s
1) The prerequisite for obtaining the given response times is an air flow > 1m/s; the response time
indicated is equal to one time constant corresponding to 63 % of the steady value
2.4. Parameters of analogue output
Output type
voltage
Output range
0-5 V or 0-10 V
Resolution
11.5 bit
in [mV] for the range 0-10 V
3.2mV~
in [mV] for the range 0-5 V
1.6mV~
Loading capacity
RL > 1 kΩ
Refreshing period
1 s