Start signal selection
F102
2
2:Communication(RS485)
Converter's address in Modbus
Network
P702
2
Air-supply fan
3
Air-exhaust fan
5
Air-supply fan No.2 / redundant
7
Air-supply fan No.3
9
Air-supply fan No.4
6
Air-exhaust fan No.2/ redundant
8
Air-exhaust fan No.3
10
Air-exhaust fan No.4
Action of RS485
communication error
P703
2
0: No warning
1: Warning, display Co
2: Display Co and stop
Communication parameters as below: Modbus RS-485, 9600 8N1,
Wire the communication terminal of the VTS5000D inverter according to the Figure 3
CAUTION! It is recommended to apply an automatic procedure for the converters' configuration, which is
available in advanced options of the HMI Advanced panel.
NOTE! To restore VTS5000D to default settings set P117 = 8 and switch off the power supply.