Cov lus qhia
Use FWD/REV/S1/S2 inputs to set desired drive function (1=on,0=off)
0000 = STOP
1100 = START, 1ST SPEED
Value is P503
1110 = START, 2ND SPEED
Value is P503+P504
1111 = START, 3RD SPEED
Value is P503+P504+P505
NOTE! If the AHU is equipped with more than 1 fan, follow Figure 2b for proper cabling.
4. AHU WITH VTS CONTROLS TYPE: VS … CG ACX36 EVO … or VS … CG uPC …
- Set additional parameters:
Parameter
Code
Value
Comments
Main frequency source X
selection
P101
5
5: RS485 communication
frequency setting