Cov lus qhia

2.2 Remote control with three speeds
- Set additional parameters:
Parameter
Code
Value
Comments
Main frequency source X selection
P101
6
Multi-speed
Start signal selection
F102
1
0: Operation panel
(FWD/REV/STOP)
1: I/O terminal
2:Communication(RS485)
SET multi function terminal REV
P316
9
Multi -speed 1
SET multi function terminal S1
P317
10
Multi -speed 2
SET multi function terminal S2
P318
11
Multi -speed 3
Multi speed 1 (speed I)
P503
*
20 100Hz
Multi speed 2 (speed II)
P504
*
20 100Hz
Multi speed 3 (speed III)
P505
*
20 100Hz
RA,RC
P325
3
3:Alarm (stop)
Wire the I/O terminal of the VTS5000D inverter according to the Figure 1
Use FWD/REV/S1/S2 inputs to set desired drive function (1=on,0=off)
0000 = STOP
1100 = START, 1ST SPEED
Value is P503
1110 = START, 2ND SPEED
Value is P503+P504
1111 = START, 3RD SPEED
Value is P503+P504+P505
3. EXHAUST UNIT WITH VTS CONTROL SYSTEM
Parameter
Code
Value
Comments
Main frequency source X selection
P101
6
Multi-speed
Start signal selection
F102
1
0: Operation panel
(FWD/REV/STOP)
1: I/O terminal
2:Communication(RS485)
SET multi function terminal REV
P316
9
Multi -speed 1
SET multi function terminal S1
P317
10
Multi -speed 2
SET multi function terminal S2
P318
11
Multi -speed 3
Multi speed 1 (speed I)
P503
*
20 100Hz
Multi speed 2 (speed II)
P504
*
20 100Hz
Multi speed 3 (speed III)
P505
*
20 100Hz
RA,RC
P325
3
3:Alarm (stop)
Wire the I/O terminal and the terminal X3 of the control box CG according to the Figure 2a