Cov lus qhia
CONTROL AND MODBUS COMMUNICATION
APPENDIX TO THE VTS5000D MANUAL ITEMS AS FOLLOW:
Index Number
Description
Sanyu Customized Model
1-2-1208-5024
FC 0,75kW 3PH 3~400V VFD
VTS5000D-0R7G-4
1-2-1208-5025
FC 1,5kW 3PH 3~400V VFD
VTS5000D-1R5G-4
1-2-1208-5026
FC 2,2kW 3PH 3~400V VFD
VTS5000D-2R2G-4
1-2-1208-5033
0,75kW 1PH 1~230V VFD_S2
VTS5000D-0R7G-S2
1-2-1208-5034
1,5kW 1PH 1~230V VFD_S2
VTS5000D-1R5G-S2
1-2-1208-5035
2,2kW 1PH 1~230V VFD_S2
VTS5000D-2R2G-S2
THE FOLLOWING MANUAL ASSUMES GOOD KNOWLEDGE OF TECHNICAL
DOCUMENTATION INCLUDED WITH THE AIR HANDLING UNIT (AHU).
THIS MANUAL CONSIDERS ONLY THE CONTROL AND COMMUNICATION CIRCUITS.
THE INSTALLATION OF THE FREQUENCY CONVERTER AND INSTALLATION OF MAINS
AND MOTOR CABLES SHOULD BE DONE ACCORDING TO THE VTS5000D MANUAL.
1. FOR ALL CONFIGURATIONS SET THE COMMON PARAMETER LIST
Parameter
Code
Value
Comments
Maximum frequency
P105
100
Acceleration Time 1
P107
45
recommended 45 sec.
Deceleration Time
P108
45
recommended 45 sec.
Rated motor voltage
P209
380
0-500V
Rated motor current
P210
*
Scale: 0.1 A
Motor rated speed
P212
*
Number of motor poles
P213
*
Rated motor slip
P214
**
0.1HZ
Rated motor frequency
P215
50
Motor overload protection
selection
P816
1
0: Prohibit
1: Permit
2. CONFIGURATIONS WITHOUT VTS CONTROLS
2.1 Local control using integrated control panel
Set additional parameters:
Parameter
Code
Value
Comments
Main frequency source X
selection
P101
3
Local keypad
potentiometer setting
mode
Start signal selection
F102
0
0: Operation panel
(FWD/REV/STOP)
1: I/O terminal
2:Communication(RS485)
Maximum frequency
P105
100
Minimum frequency
P106
20
Switch AI jumper to I to choose analog current input
AI minimum voltage input
P300
0V
0.00V~P301
AI maximum voltage input
P301
10V
Use the RUN and STOP/RST buttons to control the drive
Use buttons to set frequency