- 78 -
F8.00
Operation
monitoring
parameter
selection
For example: F8.00 = 2, that is, select the
output voltage (d-02), and then the default
display item of the main monitoring
interface is the current output voltage value.
026
0
F8.01
Selection of
shutdown
monitoring
parameter
items
For example: F8.01 = 3, that is, select the
bus voltage (d-03), and then the default
display item of the main monitoring
interface is the current bus voltage value.
026
1
F8.02
Motor speed
display
coefficient
It is used to correct the display error of the
speed scale and has no effect on the actual
speed.
0.0199.99
1.00
F8.03
Parameter
initialization
0: No operation
The inverter is in the normal parameter
reading and writing state. Whether the
setting value of the function code can be
changed depends on the setting state of the
02
0
×