User Manual
VTS2000 Series frequency inverter
- 70 -
detection
value
smaller than the feedback disconnection detection
value, the inverter will make corresponding
protection actions according to the setting of F5.00,
and it will be invalid when F5.08 = 0.0%.
F5.09
Feedback
disconnection
detection time
The delay time before the protection action after
feedback disconnection occurs.
0.1~999.9S
10.0s
×
F5.10
Inverter
overload
pre-alarm
level
The current threshold of the inverter overload
pre-alarm action is set as a percentage of the
inverter's rated current.
0~150%
120%
○
F5.11
Inverter
overload
pre-alarm
delay
The delay time between the inverter output current
and the overload pre-alarm level (F5.10) to the
output of the overload pre-alarm signal.
The delay time from the output current of the
inverter is continuously greater than the overload
pre-alarm level (F5.10) to the output of the overload
0.0~15.0s
5.0s
×