User Manual

VTS2000 Series frequency inverter
- 69 -
F5.03
Deceleration
voltage limit
factor
This parameter is used to adjust the inverter's ability
to suppress overvoltage during deceleration
0close1
255
1
×
F5.04
Overvoltage
limit level
The overvoltage limit level defines the operating
voltage during overvoltage stall protection
350400/660
850V
375/790
V
×
F5.05
Acceleration
current limit
factor
This parameter is used to adjust the inverter's ability
to suppress overcurrent during acceleration.
0close199
10
×
F5.06
Constant
speed current
limiting factor
This parameter is used to adjust the inverter's ability
to suppress overcurrent during constant speed
operation
0close110
0
×
F5.07
Current limit
level
The current limiting level defines the current
threshold of the automatic current limiting action,
and its set value is a percentage relative to the rated
current of the inverter.
50%~250
180%
×
F5.08
Feedback
disconnection
This value is the percentage of PID given amount.
When the feedback value of PID continues to be
0.0100.0%
0.0
×