User Manual
VTS2000 Series frequency inverter
- 64 -
when entering
sleep and the
set pressure
F3.15
Pipe Burst
detection
delay time
Set delay time of the pipe burst detection
0.0~130.0s
30.0S
○
F3.16
High pressure
detection
threshold
When the feedback pressure is greater than or equal
to this set value, the burst pipe fault "EPA0" will be
reported after F3.15 burst pipe delay. When the
feedback pressure is less than this set value, the
burst pipe fault "EPA0" will be automatically reset;
the threshold is the percentage of constant pressure.
0.0~200.0%
150.0%
○
F3.17
Low pressure
detection
threshold
When the feedback pressure is less than this set
value, the burst pipe fault "EPA0" will be reported
after F3.15 burst pipe delay. When the feedback
pressure is greater than or equal to this set value, the
burst pipe fault "EPA0" will be automatically reset;
0.0~200.0%
50.0%
○