- 61 -
immediately.
F3.01
Digital setting
of Given value
Use the operation keyboard to set the given value of
PID control. This function is valid only when the
digital setting of the PID given channel selects
digital setting (F3.00 tens place is 1 or 2). If the tens
place of F3.00 is 2, it is given by pressure. This
parameter is consistent with the unit of F3.18.
0.0100.0%
0.0%
F3.02
Feedback
channel gain
When the level of the feedback channel and the set
channel are inconsistent, this function can be used to
adjust the gain of the feedback channel signal.
0.0110.00
1.00
F3.03
Proportional
gain P
The speed of PID adjustment speed is set by the two
parameters of proportional gain and integration time.
If fast adjustment speed asked, it needs to increase
the proportional gain and reduce the integration
time. If slow adjustment speed asked, it needs to
reduce the proportional gain and increase the
integration time. In general, the derivative time is
0.015.00
2.00
F3.04
Integration
time Ti
0.150.0s
1.0s
F3.05
Differential
time Td
0.110.0s
0.0s