User Manual

VTS2000 Series frequency inverter
- 51 -
current
F2.06
ACI lower
limit
corresponding
setting
Set the corresponding setting of the upper and lower
limits of ACI, which corresponds to the percentage
of upper limit frequency [F0.05].
-100.0%
100.0%
0.0%
F2.07
ACI upper
limit
corresponding
setting
100.0%
F2.08
Analog input
signal filtering
time constant
This parameter is used to filter the input signal of
AVI, ACI and panel potentiometer to eliminate the
influence of interference
0.15.0s
0.1s
F2.09
Analog input
anti-shake
deviation limit
When the analog input signal frequently fluctuates
around the given value, you can set F2.09 to
suppress the frequency fluctuation caused by this
fluctuation.
0.000.10V
0.00V
F2.10
AO analog
0: output frequency
05
0