User Manual

VTS2000 Series frequency inverter
- 45 -
1do not storage
F1.17
Multi-speed
frequency 1
F1.17-P1.35 to determine the operating frequency,
time and direction of each section.
The multi-step speed frequency can be set
continuously from -upper limit frequency (-fmax) to
upper limit frequency (fmx).
Note: The sign of the multi-step speed determines
the running direction of the simple PLC. Negative
values indicate reverse operation. This machine can
set 7-step speed frequency, corresponding to
multi-step speed frequency 0 (f0) to multi-step speed
6 (f6)
Speed
segment
Multi-sp
eed S1
Multi-sp
eed S2
Multi-sp
eed S3
0
1
0
0
1
0
1
0
2
1
1
0
-Upper
frequency to
upper frequency
5.0Hz
F1.18
Multi-speed
frequency 2
--Upper
frequency to
upper frequency
10.0Hz
F1.19
Multi-speed
frequency 3
-Upper
frequency to
upper frequency
15.0Hz
F1.20
Multi-speed
frequency 4
-Upper
frequency to
upper frequency
20.0Hz
F1.21
Multi-speed
frequency 5
-Upper
frequency to
upper frequency
25.0Hz
F1.22
Multi-speed
-Upper
37.5Hz