User Manual
VTS2000 Series frequency inverter
- 35 -
LED tens: Keep down
0:Keep
1:Do not keep
LED hundreds: UP / DOWN negative frequency
adjustment
0:useless
1:useful
LED thousands: PID, PLC frequency superposition
selection
0:useless
1:F0.03+PID
2:F0.03+PLC
F0.10
acceleration
time
The time required for the inverter to accelerate from
0 to the maximum output frequency
0.1~999.9S
0.4~4.0KW
7.5S
5.5~7.5KW
15.0S
Model
setting
○
F0.11
deceleration
time
The time required for the inverter to decelerate from
the maximum output frequency to 0