4 Peripheral equipment selection
For inverters of different power levels, the recommended values of air switch MCCB, contactor capacity and copper
core insulated conductor cross-sectional area are shown in the table below
Recommended table of inverter input and output wiring specifications
Model
Incoming protection
Power cable
Signal line(mm)
Air switch MCCB
(A)
Contactor (A)
Power lien
(mm2)
Motor line
(mm2)
VTS2000-0R7G-S2
16
10
1.5
1.5
≥0.5
VTS2000-1R5G-S2
20
16
2.5
1.5
≥0.5
VTS2000-2R2G-S2
32
20
4.0
2.5
≥0.5
VTS2000-0R7G-4
10
10
1.0
1.0
≥0.5
VTS2000-1R5G-4
16
10
1.0
1.0
≥0.5