Owner's Manual
WING W100-200
WING E100-200
WING C100-200
14
8.2. ELECTRIC AIR CURTAIN – WING E100-200
T
p1
– temperature of air at the inlet to the device
T
p2
– temperature of air at the outlet from the device
P
g
– heating output of the device
Parameters
WING E100
WING E150
WING E200
T
p1
[°F]
41
50
59
68
41
50
59
68
41
50
59
68
III/1088[CFM]/59dB(A)*
III/1854[CFM]/61dB(A)*
III/2648[CFM]/62dB(A)*
P
g
[kW]
2/4/6
2/4/6
2/4/6
2/4/6
4/8/12
4/8/12
4/8/12
4/8/12
6/9/15
6/9/15
6/9/15
6/9/15
T
p2
[°F]
46/51/59
55/60/68
64/69/77
73/78/86
48/53/59
57/62/68
66/71/77
75/80/86
48/50/57
57/59/66
66/68/75
75/77/84
II/824[CFM]/48dB(A)*
II/1206[CFM]/48dB(A)*
II/1883[CFM]/48dB(A)*
P
g
[kW]
2/4/6
2/4/6
2/4/6
2/4/6
4/8/12
4/8/12
4/8/12
4/8/12
6/9/15
6/9/15
6/9/15
6/9/15
T
p2
[°F]
48/53/60
57/62/69
66/71/78
75/80/87
50/57/66
59/66/75
68/75/84
77/84/93
50/53/60
59/62/69
68/71/78
77/80/87
I/541[CFM]/44dB(A)*
I/853[CFM]/43dB(A)*
I/1265[CFM]/45dB(A)*
P
g
[kW]
2/4/6
2/4/6
2/4/6
2/4/6
4/8/12
4/8/12
4/8/12
4/8/12
6/9/15
6/9/15
6/9/15
6/9/15
T
p2
[°F]
51/60/69
60/69/78
69/78/87
78/87/96
55/66/78
64/75/87
73/84/96
82/93/105
53/59/69
62/68/78
71/77/87
80/86/96
8.3. WING C100-200 – COLD AIR CURTAIN
Parameters
WING C100
WING C150
WING C200
Fan speed
III
II
I
III
II
I
III
II
I
Qp [CFM]
1147
882
618
1883
1324
882
2707
2001
1377
noise level [dB(A)]*
62
49
45
63
49
43
63
49
45
* The noise level has been measured within a 10 ft distance from the device; reference conditions: semi-open space – wall-mounted device.
Parameters
WING W100-200
WING E100-200
WING C100-200
unit of
measure
W100
W150
W200
E100
E150
E200
C100
C150
C200
Maximum width of a single door for one
device
in
39
59
79
39
59
79
39
59
79
Maximum height of door
ft
12
13
Heating output range
MBH
13 –
58
34 – 109
58 –
160
7/20 or 14/20
13/41
or
27/4
1
20/51 or
30/51
-
Maximum flow rate
CFM
1089
1824
2589
1088
1854
2648
1147
1883
2707
Maximum temperature of heating
medium
°F
200
-
-
Maximum working pressure
psi
232
-
-
Water volume
in³
97
158
219
-
-
Diameter of stub pipe connectors
"
3/4
-
-
Supply voltage
V/ph/Hz
~240/1/(50/6
0)
~240/1/(50/60)
or
~240/3/(50/60)
or
~480/3/(50/60)
~240/3/(50/60) or
~480/3/(50/60)
~240/1/(50/6
0)
Power of the electric heater
kW
-
2 and 4
4 and 8
6 and 9
-
Rated current of the electric heater
A
-
9 or
5/10/15 or
3/5/8
10/20/30 or
5/10/15
15/22/37 or
8/11/19
-
-
-
EC Engine power
HP
0,27
0,4
0,64
0,27
0,4
0,64
0,27
0,4
0,64
EC engine rated current
A
1.5
2.2
3.5
1.5
2.2
3.5
1.5
2.2
3.5
Weight
lbs
47
64
83
49
67
86
42
56
72
IP
-
20
EN