Owner's Manual

WING W100-200
WING E100-200
WING C100-200
14
8.2. ELECTRIC AIR CURTAIN WING E100-200
T
p1
temperature of air at the inlet to the device
T
p2
temperature of air at the outlet from the device
P
g
heating output of the device
Parameters
WING E100
WING E150
WING E200
T
p1
[°F]
41
50
59
68
41
50
59
68
41
50
59
68
III/1088[CFM]/59dB(A)*
III/1854[CFM]/61dB(A)*
III/2648[CFM]/62dB(A)*
P
g
[kW]
2/4/6
2/4/6
2/4/6
2/4/6
4/8/12
4/8/12
4/8/12
4/8/12
6/9/15
6/9/15
6/9/15
6/9/15
T
p2
[°F]
46/51/59
55/60/68
64/69/77
73/78/86
48/53/59
57/62/68
66/71/77
75/80/86
48/50/57
57/59/66
66/68/75
75/77/84
II/824[CFM]/48dB(A)*
II/1206[CFM]/48dB(A)*
II/1883[CFM]/48dB(A)*
P
g
[kW]
2/4/6
2/4/6
2/4/6
2/4/6
4/8/12
4/8/12
4/8/12
4/8/12
6/9/15
6/9/15
6/9/15
6/9/15
T
p2
[°F]
48/53/60
57/62/69
66/71/78
75/80/87
50/57/66
59/66/75
68/75/84
77/84/93
50/53/60
59/62/69
68/71/78
77/80/87
I/541[CFM]/44dB(A)*
I/853[CFM]/43dB(A)*
I/1265[CFM]/45dB(A)*
P
g
[kW]
2/4/6
2/4/6
2/4/6
2/4/6
4/8/12
4/8/12
4/8/12
4/8/12
6/9/15
6/9/15
6/9/15
6/9/15
T
p2
[°F]
51/60/69
60/69/78
69/78/87
78/87/96
55/66/78
64/75/87
73/84/96
82/93/105
53/59/69
62/68/78
71/77/87
80/86/96
8.3. WING C100-200 COLD AIR CURTAIN
Parameters
WING C100
WING C150
WING C200
Fan speed
III
II
I
III
II
I
III
II
I
Qp [CFM]
1147
882
618
1883
1324
882
2707
2001
1377
noise level [dB(A)]*
62
49
45
63
49
43
63
49
45
* The noise level has been measured within a 10 ft distance from the device; reference conditions: semi-open space wall-mounted device.
Parameters
WING W100-200
WING E100-200
WING C100-200
unit of
measure
W100
W150
W200
E100
E150
E200
C100
C150
C200
Maximum width of a single door for one
device
in
39
59
79
39
59
79
39
59
79
Maximum height of door
ft
12
13
Heating output range
MBH
13
58
34 109
58
160
7/20 or 14/20
13/41
or
27/4
1
20/51 or
30/51
-
Maximum flow rate
CFM
1089
1824
2589
1088
1854
2648
1147
1883
2707
Maximum temperature of heating
medium
°F
200
-
-
Maximum working pressure
psi
232
-
-
Water volume
in³
97
158
219
-
-
Diameter of stub pipe connectors
"
3/4
-
-
Supply voltage
V/ph/Hz
~240/1/(50/6
0)
~240/1/(50/60)
or
~240/3/(50/60)
or
~480/3/(50/60)
~240/3/(50/60) or
~480/3/(50/60)
~240/1/(50/6
0)
Power of the electric heater
kW
-
2 and 4
4 and 8
6 and 9
-
Rated current of the electric heater
A
-
9 or
5/10/15 or
3/5/8
10/20/30 or
5/10/15
15/22/37 or
8/11/19
-
-
-
EC Engine power
HP
0,27
0,4
0,64
0,27
0,4
0,64
0,27
0,4
0,64
EC engine rated current
A
1.5
2.2
3.5
1.5
2.2
3.5
1.5
2.2
3.5
Weight
lbs
47
64
83
49
67
86
42
56
72
IP
-
20
EN