Owner's Manual

Recommended safety devices and wires
Device
WING E100-200
E100
E150
E200
Supply voltage 1~240V
MCB
35A
MCA
33.5A
FLA
27.1A
Power wire cross-section
3 x 10 AWG
Cable Nominal Voltage UL/CSA 600 V
Supply voltage 3~240V
MCB
25A
45A
55A
MCA
20.5A
38.8A
49.8A
FLA
16.7A
32A
40.6A
Power wire cross-section
5 x 12 AWG
5 x 10 AWG
5 x 8 AWG
Cable Nominal Voltage UL/CSA 600 V
Supply voltage 3~480V
MCB
15A
25A
30A
MCA
11A
20.2A
26.7A
FLA
9.1A
17.2A
22.1A
Power wire cross-section
5 x 14 AWG
5 x 12 AWG
5 x 12 AWG
Cable Nominal Voltage UL/CSA 600 V
IMPORTANT! The specification of cables and protections refers to unbounded arrangement of. One should always abide by the local laws and recommendations concerning device connection.
WING is equipped with a terminal strip adjusted to an appropriate thickness of wires.
Air curtain model
Terminals view
Terminals description and function
WING E100 240/1/60 EC
L1 Power supply phase
L2 Power supply phase
Ground
1L1 N/C
L2 N/C
2 first heating stage controlled by applying
240VAC
3 second heating stage controlled by applying 240VAC
Ai 0-10VDC analog input for fan speed regulation
G Reference ground for 0-10VDC speed regulation
connected internally
1L1 connected internally
L2 connected internally
WING E100 240/3/60 EC
L1 Power supply phase
L2 Power supply phase
L3 Power supply phase
Ground
1L1 N/C
L2 N/C
2 first heating stage controlled by applying
240VAC
3 second heating stage controlled by applying 240VAC
Ai 0-10VDC analog input for fan speed regulation
G Reference ground for 0-10VDC speed regulation
connected internally
L1 connected internally
L2 connected internally
WING E100 480/3/60/HLD EC
L1 Power supply phase
L2 Power supply phase
L3 Power supply phase
Ground
1L1 N/C
L2 N/C
2 first heating stage controlled by applying
240VAC
3 second heating stage controlled by applying 240VAC
Ai 0-10VDC analog input for fan speed regulation
G Reference ground for 0-10VDC speed regulation
connected internally
1L1 connected internally
2L2 connected internally
WING E150 240/3/60 EC
WING E200 240/3/60 EC
L1 Power supply phase
L2 Power supply phase
L3 Power supply phase
Ground
1L1 N/C
L2 N/C
2 first heating stage controlled by applying
240VAC
3 second heating stage controlled by applying 240VAC
Ai 0-10VDC analog input for fan speed regulation
G Reference ground for 0-10VDC speed regulation
connected internally
1L1 connected internally
L2 connected internally
WING E150 480/3/60/HLD EC
WING E200 480/3/60/HLD EC
L1 Power supply phase
L2 Power supply phase
L3 Power supply phase
Ground
1L1 N/C
L2 N/C
2 first heating stage controlled by applying
240VAC
3 second heating stage controlled by applying 240VAC
Ai 0-10VDC analog input for fan speed regulation
G Reference ground for 0-10VDC speed regulation
connected internally
1L1 connected internally
2L2 connected internally
WING W100 240/1/60 EC
WING W150 240/1/60 EC
WING W200 240/1/60 EC
L1 Power supply phase
L2 Power supply phase
Ground
1L1 N/C
L2 N/C
2 input signal form HMI to control on/off valve
9 valve with actuator Control
10 valve with actuator control
Ai 0-10VDC analog input for fan speed regulation
G Reference ground for 0-10VDC speed regulation
connected internally
1L1 connected internally
L2 connected internally
WING C100 240/1/60 EC
WING C150 240/1/60 EC
WING C200 240/1/60 EC
L1 Power supply phase
L2 Power supply phase
Ground
L1 N/C
L2 N/C
Ai 0-10VDC analog input for fan speed regulation
G Reference ground for 0-10VDC speed regulation
connected internally
1L1 connected internally
L2 connected internally
Device
WING W100-200 and WING C100-200
W/C100
W/C150
W/C200
Fan supply voltage 1~240V
MOP
15
15
15
MCA
1.9A
2.8A
4.4A
FLA
1.5A
2.2A
3.5A
Power wire cross-section
3 x 14 AWG
Cable Nominal Voltage UL/CSA 600 V