Installation & User Guide
HMI WING UL (1-4-2801-0223), Rev 17
A0
Modes of automatic operation:
room [0], door [1], door+room
[2]
selection [0, 1, 2]
A1
Regulation of the heating power
level:
without heating [0], first level [1],
second level [2], third level [3]
Selection [0, 1, 2, 3]
A2
Temp. sensor calibration
max. ±8°C with the step of 0.5°C
A3
Heating mode:
Heating [0], ventilation [1],
heating+ventilation [2]
Selection [0, 1, 2]
A4
Hysteresis of differential
adjuster
0.5/1/2
A5
First speed value
15-80%
A6
Second speed value
15-90%
A7
Third speed value
15-100%
A8
Fan speed delay
30….200s
A9
Backlight time
5….600s
AA
Door optimum
0, +1, +2, +3
AB
Door sensor logic
NO [0], NC [1]
AC
Mim. Fan speed during cooling
down
45-100%
AD
Min. fan speed
Only display
AE
Calendar-based work
No [0], Yes [1]
AF
Time mode
12h [1]; 24h [0]
B0
Buttons blockade
selection
B1
Extra heating time
0….90s
Bo
Default settings
Hold
Note. The Door optimum function (AA) allows increase the fan
speed from currently set one in case of door opening:
‘’+1” – increases the fan speed by one step when door iw
open
‘’+2” – increases the fan speed by two step when door iw
open.
Anytime you ned to disable the “Door optimum” function, just set it
to the ‘’+0” setting.
.
7.2. ADVANCED SETTINGS, SECTION C
To enter the advanced settings C of this controller, press and hold
the [Set] button for 5 seconds at the deactivated controller. Toggle
between parameters using [Set] button. Change the value or
settings of selected parameters using [^] and [v] buttons. After
changes are applied, leave the settings mode by pressing power
button of the controller.
Your settings will be saved automatically. For advanced settings
A group, the following parameters can be modified:
No.
Function
Set point
B0
Temperature units
°C/°F
B1
Min. Temperature
41 … 104
o
F (5….15 °C)
B2
Max. Temperature
61 … 104
o
F (16….40 °C)
B3
Communication Modbus
RTU – speed
2400/4800/9600 kbps.
B4
Communicatin Modbus
RTU – parity
None/ odd/ even
8. TECHNICAL SPECIFICATION
Power supply
o 1*120-230 VAC 60 Hz
Power consumption
o 1.5 VA
Features of the automatic action
o Type 1 Action, Type 1.B Action (UL 60730-1)
Maximum current on relay outputs
o 5 A (max 2.5 A on each circuit)
Load type
o Resistive, PF ≥ 0.95
RS485 port voltage / current limitation
o -7… +12V / ±250 mA
Temperature sensor type
o NTC, 10 kΩ @ 77 °F (25 °C)
Measured temperature range
o 32 °F … 122 °F, (0 °C ... 50 °C)
Temperature measurement precision
o ±0.9
o
F (±0.5 °C)
Communication
o Relay output: Dual - NO, 250 V, 5 A: 105 cycles, AgNi
@ 85 °C; 5 x 104 cycles, AgSnO2 @ 85 °C
o Analog output: 0-10V (8 bit, Imax = 20 mA)
o Modbus RTU, 2400/4800/9600 bps,
Working conditions limits
o Temperature range: 32 °F … 122 °F (0 °C ... 50 °C)
o Relative humidity: 10-90% with no condensation.
Storage conditions limits
o Temperature range: -4 °F … 122 °F (-20 °C ... 50 °C)
o Relative humidity: 10-90% with no condensation.
Ingress Protection
o IP20
Pollution Degree
o 2
Max working altitude
o 6 000 ft (2 000 m) AMSL
Construction and installation
o Independently Flush-mounted. Flush Mount Junction
Box, min 1-1,2” deep. Mounting bracket provided (a part
of the controller assembly).
Maximum mechanical load on the controller installation
(flush-mounting)
o Parallel to the the wall, downwards, both sides: 5 N
o Parallel to the the wall, upwards (front panel
unmounting direction), both sides: 2 N
o Perpendicular to the wall: 5 N
Dimension
o 3-3/8" x 3-3/8" x 1-7/8" (86 x 86 x 48 mm)
Weight
o 5.3 oz (150 g).