Installation & User Guide

HMI WING UL (1-4-2801-0223), Rev 17
6.4. MAIN SETTINGS
No.
Description
Operation button
1
Heating mode*:
Operation of single heater coils sections
Operation of two heater coils sections
Function A1
[^] or [v]
2
Calendar-based work:
Yes ;
No
Function AE
[^] or [v]
3
Operating mode:
heating: ;
ventilation ;
heating + ventilation + ;
Function A3
[^] or [v]
4
Temperature display:
ROOM (current temp.),
SET (set temp.)
EXT (based on external temperature
sensor)
Function A1
[^] or [v]
5
Day of the week
Hold
[Set]+[v]
6
Hour, minute
Hold
[Set]+[v]
7
Screen lock
Hold
[v]
8
Door close/open
n/a
*Note
Minimum fan activation percentage for engaging the heating
function is 60% (6 Volts on the analog signal output).
Explanation of the operating modes:
Speed I: Programmable value in the range of 15-80%.
Speed II: Programmable value in the range of 15-90%.
Speed III: Programmable value in the range of 15-100%.
Press to change the fan speed.
The values of the individual gears can be set from the advanced
settings A: function A5, A6 and A7.)
6.5. TIME SCHEDULE SETTINGS
6.5.1. TIME/DAY SETTING
You can set the present time and day on the controller. To do it,
press and hold the [Set] button and the arrow down button. The
controller will enter the time/day settings mode allowing you to set
present time and day of the week.
6.5.2. SCHEDULE SETTING
Having the controller in active mode, press the [Set] button and
hold it for 5 seconds. The controller will enter the time (weekly)
schedule settings mode.
Use the [Set} button to toggle between schedule functions [^] and
[v] buttons to change the value.
The weekly schedule can be set for each day of the week and 4-
time intervals for each day.
Your schedule settings will be demonstrated on the graphical time
chart like on Figure 7
7. PROGRAMMING MODE
7.1. ADVANCED SETTINGS, SECTION A & B
To enter the advanced settings A of this controller, press and hold
the [ ] button for 5 seconds at the deactivated controller. Toggle
between parameters using [Set] button. Change the value or
settings of selected parameters using [^] and [v] buttons. After
changes are applied, leave the settings mode by pressing power
button of the controller. Your settings will be saved automatically.
For advanced settings A group, the following parameters can be
modified:
No.
Function
Set point
IP
Communication Modbus RTU -
address
1 ... 254
Figure 7 - Time schedule chart