Installation & User Guide
HMI WING UL (1-4-2801-0223), Rev 17
5.4. CONNECTION OF HMI WING UL CONTROLLER TO WING E100/150/200 480/3/60 MODELS.
Connect the HMI WING UL to the WING E100/150/200 480/3/60 air curtains according to diagram shown on Figure 5.
Figure 5 - WING E100/150/200 480/3/60 connections.
5.5. CONNECTION OF HMI WING UL CONTROLLER TO WING C100/150/200 240/1/60 MODELS.
Connect the HMI WING UL to the WING C100/150/200 240/1/60 air curtains according to diagram shown on Figure 6.
Figure 6 - WING C100/150/200 240/1/60
5.6. CONTROLLER FLUSH MOUNTING
Apply the following sequence of actions while flush-mounting of this controller:
Install the flush mounted junction box (1)
Cross all cables through the junction box and prepare their ends for plugging into
controller’s terminal block (remove the shields and apply end sleeves if justified)
Plug the wires into the controller’s terminal block according to relevant wiring diagram
(above listed). Ensure that cables are properly plugged and are not loose.
Install the rear power part of the controller in the flush mounted junction box and tight
both sides screws (2)
Plug the strip cable to the terminal in the front part of controller (3)
Mount the front part of the controller on the rear one (4)
CAUTION. After all installation works, check if the flash mounting is properly done (the
controller is fixed in the wall and is not loose).
5.7. OTHER INSTALLATION FACTS AND
RECOMMENDATIONS
Type of flush mounting junction box:
o Flush mounted junction box Ø 60 mm, minimum depth
of the box: 1-1,2”
Flush mounted part of the controller:
o Rear power supply unit
Minimum height of the installation
o 5 feet above floor level
Minimum clearance between the controller (side edges of
the front display part) and the surrounding parts of the
fitment:
o 4”
The minimum dimensions of ventilating openings and their
correct arrangements
o N/A