Owner's Manual
8
* for vertical air guides adjustment
Volcano VR3
fan speed
III
II
I
air flow
CFM
3355
2413
1766
noise level for Volcano EC*
dB(A)
55
49
43
EC motor electric power**
HP
0,48
0,37
0,28
horizontal air stream range
ft
82
72
56
vertical air stream range
ft
39
30
23
* reference conditions: room volume 52 972 ft³, measurement taken at a distance of 16ft
** EC motor electric power for the air flow mentioned in the table
Volcano VR-D
fan speed
III
II
I
air flow
CFM
3826
2707
2001
noise level for Volcano EC*
dB(A)
56
50
43
EC motor electric power**
HP
0,48
0,37
0,28
horizontal air stream range
ft
92
79
62
vertical air stream range
ft
49
36
30
* reference conditions: room volume 52 972 ft³, measurement taken at a distance of 16ft
** EC motor electric power for the air flow mentioned in the table
4. ASSEMBLY
NOTE Installation location should be suitably selected with special consideration of potential loads and vibrations.
Prior to any installation or maintenance works, disconnect the device from the power supply and secure it against accidental power-up.
Use filters in the hydraulic system. Before you connect the hydraulic lines (especially supply lines) to the device, you should clean/rinse the
installation by draining two litres out of it.
NOTE It is necessary to maintain a minimum distance of 0.4m from the wall or the ceiling; otherwise the device can malfunction, the fan can be
damaged or its operating noise can increase.
If the device will be installed on a wall or under a ceiling, observe the following factors:
mounting heigh
distance between units – recommended distance 19,6-39ft (Volcano VR1, VR2, VR3), 9,8-23ft (Volcano VR Mini), in order to ensure even hot air
diffusion
* for vertical air guides adjustment
OPT. 6,5 - 16ft (Volcano VR Mini)
OPT. 8,2 – 26ft (Volcano VR1, VR2, VR3)
OPT. 9,8 - 23ft
(Volcano VR Mini)
OPT. 19,6 – 39ft
(Volcano VR1, VR2, VR3)