Installation guide
Acme Packet 6100 Hardware Installation and Maintenance Guide 49
1. Set the System Power switch to the Stby position to cut off power to the
Acme Packet 6100.
USBAlarmConsole
System
Power
On
Stby
Stby
DIS
Figure 4 - 71. AC Power Supplies (left) and System Power Switch (right)
2. Locate the two AC power cords shipped with your Acme Packet 6100.
Choose one power supply to work on first.
3. Connect one power cord to the power supply by inserting the 3-lead IEC-
60
320 plug into the IEC connector located on the power supply.
Mgmt 0USBAlarmConsole
System
Power
On
Stby
Stby
Dis
Figure 4 - 72. Plug in One AC Power Cord
4. Connect the other power cord to the power supply by inserting the 3-lead
IEC-60320 C13 plug into the IEC-60320 C14 IEC connector located on the
power supply.
AlarmConsole
System
Power
On
Stby
Stby
Dis
Figure 4 - 73. Plug in the Second AC Power Cord
5. Route the AC power cords through your rack and cabling system to the
power outlets.
6. There is no on/off switch on these power supplies. When you plug them in
th
e power is on and the system will start to boot.
7. Plug the supply end of each power cord into its own circuit.
Note: To remove AC power cables from the Acme Packet 6100
rev
erse the previous procedure.
8. Set the System Power switch to the On position to provide power to the
Acm
e Packet 6100.