Installation guide

Handle to
Remove/Insert
Power Supply
Locking Tab to
Lock/Unlock
Power Supply to
Acme Packet
6100
Acme Packet 6100 Hardware Installation and Maintenance Guide 19
Figure 2 - 31. Acme Packet 6100 DC Power Supply
DC Power Cords A DC power cord ships with each DC power supply. A DC power cord must be
3-conductor, 10 AWG minimum rated for at least 140° F (60° C).
Table 2 - 4. Acme Packet 6100 DC Power Cord Wire Markings
Wire Color
Lead Designation (style-A DC
P
ower Supply)
Lead Designation (style-B DC
Power Supply)
Red Return +
Green/Yellow Frame Ground
Black -48 VDC -
Grounding Terminals The grounding terminals are used to attach the Acme Packet 6100 chassis to a
local earth ground. The terminals are located to the left of Power Supply B on
the rear of the Acme Packet 6100. The Acme Packet 6100 is shipped with a lug
and mounting nuts attached to the chassis along with a pre-made ground
cable. A loose lug is included with the shipment so that the user has the
potential to crimp the lug to a custom cable if desired.