User Manual 3/3 10K~30K Online UPS Uninterruptible Power Supply System Version: 1.
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ................................................................................................. 1 1-1. TRANSPORTATION AND STORAGE ...............................................................................................................1 1-2. PREPARATION.......................................................................................................................................1 1-3. INSTALLATION ...............................................
1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1-1. Transportation and Storage Please transport the UPS system only in the original package to protect against shock and impact. The UPS must be stored in the room where it is ventilated and dry. 1-2. Preparation Condensation may occur if the UPS system is moved directly from cold to warm environment.
1-4. Connection Warnings There is no standard backfeed protection inside, please isolate the UPS before working according to this circuit. The isolation device must be able to carry the UPS input current. • This UPS should be connected with TN earthing system • The power supply for this unit must be three-phase rated in accordance with the equipment nameplate.
1-5. Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
2. Installation and Operation There are two different types of online UPS: standard and long-run models. Please refer to the following model table. Model Type Model Type 10K 10KL 15K 15KL Standard Long-run model model 20K 20KL 30K 30KL We also offer optional parallel function for these two types by request. The UPS with parallel function is called as “Parallel model”. We have described detailed installation and operation of Parallel Model in the following chapter. 2-1.
2-2. Rear Panel View Diagram 1: 10K(L)/15K(L)/20K(L) Diagram 2: 30KL Rear Panel Diagram 3: 30K Rear Panel Rear Panel Diagram 3: 10K(L)15K(L)/20K(L) Diagram 4: 30K(L) Input/Output Terminal Input/Output Terminal 1. RS-232 communication port 2. USB communication port 3. Emergency power off function connector (EPO connector) 4.
5. Parallel port (only available for parallel model) 6. Intelligent slot 7. Power stage fan 8. External battery connector (Only available for long-run model) 9. Bypass Input Circuit Breaker(Only available for dual input unit) 10. Input/Output terminal (Refer to Diagram 2) 11. Line Input circuit breaker 12. Maintenance bypass switch 13. Output Grounding terminal 14. Output terminal: connect to mission-critical loads 15. Line input terminal 16. Bypass input terminal(Only available for dual input) 17.
use AWG 8 or thicker wire for Phase and AWG 4 or thicker wire for Neutral for safety and efficiency. NOTE 5: The selections for color of wires should be followed by the local electrical laws and regulations. 5) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following terminal block diagrams: (Connect the earth wire first when making wire connection.
not, please install it carefully. Switch off the battery breaker before installation. NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack. ● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the numbers of the battery pack, please make sure you modify the setting simultaneously. The connection with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
Wiring diagram of parallel system for 30K(L) 2-5. Software Installation For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
3. Operations 3-1. Button Operation Button Function ON/Enter Button Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS. Enter Key: Press this button to confirm the selection in setting menu. OFF/ESC Button Turn off the UPS: Press and hold the button more than 0.5s to turn off the UPS. Esc key: Press this button to return to last menu in setting menu. Test/Up Button Mute/Down Button Test/Up + Mute/Down Button Battery test: Press and hold the button more than 0.
LCD Panel: Display Function Backup time information Indicates the battery discharge time in numbers H: hours, M: minutes, S: seconds Fault information Indicates that the warning and fault occurs. Indicates the fault codes, and the codes are listed in details in section 3-9. Mute operation Indicates that the UPS alarm is disabled. Output & Battery voltage information Indicates the output voltage, frequency or battery voltage.
Battery information Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the battery is not connected. Indicates low battery level and low battery voltage. Input & Battery voltage information Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency 3-3.
3. Connect devices to UPS After the UPS is turned on, you can connect devices to the UPS. 1) Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total load level. 2) If it is necessary to connect the inductive loads such as a printer, the in-rush current should be calculated carefully to see if it meets the capacity of the UPS, because the power consumption of this kind of loads is too big. 3) If the UPS is overload, the buzzer will beep twice every second.
2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the line input breaker(for dual input unit, also switch off the bypass line breaker). A few seconds later, there is no display shown on the display panel and UPS is complete off. 8. Turn off the UPS without utility power supply in Battery mode 1) Turn off the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once.
3-5. Parallel Operation 1. Parallel system initial startup First of all, please make sure all of the UPSs are parallel models and have the same configuration. 1) Turn on each UPS to AC mode respectively (Refer to section 3-4(1)). Then, measure the inverter output voltage of each phase for each UPS to check if the inverter voltage difference between actual output and setting value is less than 1.5V (typical 1V) with multimeter. If the difference is more than 1.
Second method: 1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the load and shut down the system first. 2) Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance switches from “UPS” to “BPS”. Turn off all the input breakers and battery breakers in parallel system.
AB The first line BC The second line CA The third line 3-7. LCD Setting There are three parameters to set up the UPS. Refer to following diagram. Parameter 1: It’s for program alternatives. Refer to below tables for the programs to set up. Parameter 1 Parameter 2 and parameter 3 are the setting options or values for each program. Note: Please select “Up” or “Down” button to change the programs or parameters.
20 Output C voltage calibration Y Y Y *Y means that this program can be set in this mode. Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode).
04: Frequency range for bypass Interface Setting Parameter 2: Set the acceptable low frequency for bypass. 50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 60 Hz system: Setting range is from 56.0Hz to 59.0Hz. The default value is 46.0Hz/56.0Hz. Parameter 3: Set the acceptable high frequency for bypass. 50 Hz: Setting range is from 51.0Hz to 54.0 Hz. 60 Hz: Setting range is from 61.0Hz to 64.0Hz. The default value is 54.0Hz/64.0Hz.
09: Maximum battery discharge time setting Interface 10: Reserved Interface Setting Reserve for future options. 11: Reserved Interface Setting Parameter 3: 000~999: Set the maximum discharge time from 0 min to 999 min. UPS will shut down to protect battery if the discharge time arrives before the battery is under voltage. The default value is 990 min. DIS: Disable battery discharge protection and backup time will depend on battery capacity. Setting Reserve for future options.
13: Battery voltage calibration Interface 14: Charger voltage adjustment Interface Setting Parameter 2: you may choose Add or Sub to adjust charger voltage Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V. NOTE: *Before making voltage adjustment, be sure to disconnect all batteries first to get the accurate charger voltage. * Any modification should be suitable to battery specifications.
18: Output A voltage calibration Interface Setting Parameter 2: it always shows OP.V as output voltage. Parameter 3: it shows the internal measurement value of the output A voltage, and you can calibrate it by pressing Up or Down according to the measurement from an external voltage meter. The calibration result will be effective by pressing Enter. The calibration range is limited within +/-9V. This function is normally used for parallel operation.
Operating mode/status UPS Power On Description When UPS is powered on, it will enter into this mode for a few seconds as initializing the CPU and system. LCD display No-output description mode When bypass voltage/frequency is out of acceptable range or bypass is disabled (or forbidden), UPS will enter into no-output mode if powering on or turning off the UPS. It means the UPS has no output. Alarm beeps every two minutes.
ECO mode Description When the input voltage is within voltage regulation range and ECO mode is enabled, UPS will bypass voltage to output for energy saving.
CVCF mode Description When the output frequency is set to “CF”, the inverter will output constant frequency (50 Hz or 60 Hz). At this mode, the UPS will have no bypass output but still charge battery. LCD display Battery mode Description When the input voltage/frequency is beyond the acceptable range or power failure, UPS will backup power from battery and alarm will beep every 4 seconds.
Bypass mode Description When input voltage is within acceptable range and bypass is enabled, turn off the UPS and it will enter Bypass mode. Alarm beeps every two minutes. LCD display Battery Test Description When UPS is in AC mode or CVCF mode, press “Test” key for more than 0.5s. Then, the UPS will beep once and start “Battery Test”. The line between I/P and inverter icons will blink to remind users. This operation is used to check the battery status.
Warning Description status If some errors occur in the UPS (but it is still running normally), it will show one more screen to represent the warning situation. In the warning screen, the icon will be flashing, and it can show up to 3 error codes and each code indicates one error. You can find the code meaning in the warning code table. LCD display Fault status Description When UPS has fault happened, the inverter will be blocked.
3-9.
3-11.
4. Trouble Shooting If the UPS system does not operate correctly, please solve the problem by Symptom Possible cause No indication and alarm in the front The AC input power is not display panel even though the mains is connected well. normal. EPO function is activated. At The icon and the warning code this time, the EPO switch is in flash on LCD display and alarm “OFF” status or the jumper is beeps every second. open. The icon and flash on LCD display and alarm beeps every second.
Symptom The warning code 02 is shown, the icon flashes on LCD display, and alarm beeps every second. Possible cause Remedy The input neutral wire disconnected. Check and correct the input neutral connection.
5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: Storage Temperature Recharge Frequency Charging Duration -25°C - 40°C Every 3 months 1-2 hours 40°C - 45°C Every 2 months 1-2 hours 5-2. Maintenance The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
6. Specifications MODEL CAPACITY* INPUT 10K 10KL 10000VA / 9000W Low Line Comeback High Line Loss High Line Comeback Frequency Range Phase Power Factor OUTPUT Phase 208/220/230/240VAC(Ph-N) AC Voltage Regulation ± 1% Frequency Range (Synchronized Range) Frequency Range (Batt.